+86 137 5222 7265
+86 188 0644 0456

Home   >  Product Center   >  Residual Pressure Monitoring System for Evacuation Passages   >  Residual Pressure Detector   >  Residual Pressure Detector BA-YY-TA002
>
<

Residual Pressure Detector BA-YY-TA002

Model BA-YY-TA002 Residual Pressure Detector is applicable to anterooms, shared anterooms, fire elevator anterooms, enclosed refuge floors and smoke-proof stairwells. It adopts imported sensors with high measurement accuracy and complies with the latest fire acceptance standards. Featuring concise appearance and compact size, the detector is designed for high practicality and convenient construction installation.


Product Details
Specs & Params
Related Products

※ The residual pressure detector is suitable for anterooms, shared anterooms, fire elevator anterooms, enclosed refuge floors and smoke-proof stairwells.

※ Equipped with imported high-precision sensors, fully compliant with the latest fire acceptance standards.

※ Compact structure with neat and streamlined appearance.

※ Practical structural design for easy field installation.

※ Automatic overpressure sensing function.

※ Air nozzle arranged on the rear side.

※ Optional backlit LCD digital display or display-free version.

※ Unique address code can be configured on-site via portable address encoder.



Supply VoltageDC36V
Threshold Range30~100Pa
Air Tube SizePU 4 × 2.5 × 30CM(Custom lengths available)
Operating EnvironmentTemperature: -20℃ ~ +55℃; Relative Humidity ≤93% (non-condensing)
Operating Pressure (Anteroom/Corridor)30Pa,Reset Pressure 25Pa
Operating Pressure (Stairwell/Corridor)50Pa,Reset Pressure 40Pa
Installation MethodEmbedded wall junction box
Overall Dimensions86mm*86mm*20mm

Online

Phone

+86 137 5222 7265
+86 188 0644 0456

WeChat

Email

intl.trade@sdbenan.com

Top