+86 137 5222 7265
+86 188 0644 0456

Home   >  Product Center   >  Gas Alarm System   >  Point-type Combustible Gas Detector for Industrial and Commercial Use   >  GT-SST613 LED Point-type Combustible Gas Detector
>
<

GT-SST613 LED Point-type Combustible Gas Detector

Detected Gas:Methane

Detection Principle:Catalytic Combustion, Infrared

Display Type:None

Product Dimensions:148mmx155mmx75mm

Explosion-Proof Mark:Ex db ll C T6 Gb; Ex tb lllC T80°C Db

Executive Standard:GB 15322.1-2019

GT-SST613LED点型可燃气体探测器

Instruction Manual

Product Details
Specs & Params
Related Products

Product Description:

The GT-SST613LED gas detector continuously monitors methane gas within the lower explosive limit (LEL) range in industrial and commercial environments. It converts gas concentration and system information into current signals, which are then transmitted to the gas alarm controller system for identification, display, and processing.


Product Features:

※ The detector adopts high-quality gas-sensing components, featuring stable performance, high sensitivity, and excellent anti-toxicity resistance.

※ LED on-site status indication: green light on for "normal", yellow light on for "fault", and red light on for "alarm".

※ The sensor module features a hot-swappable design, facilitating easy installation and maintenance. After replacing the module, it can be used directly without the need for recalibration.


Application Scenarios::

Widely applied in large shopping malls, large restaurants, food processing factories, pharmaceutical factories, automobile manufacturing plants, small industrial and commercial users (small venues such as snack bars, hairdressing and beauty salons, hotels, public bathhouses and Internet cafes), farmers' markets and other industrial and commercial premises where gas leakage may occur.

Rated VoltageDC 24V
Detected GasMethane
Detection PrincipleCatalytic Combustion, Infrared
Response TimeT90 ≤ 30s
Error±3% LEL
Communication Method4-20mA
Display TypeNone
Resolution1%LEL
Power Consumption≤ 3W
Measuring Range3% LEL~100% LEL
Alarm MethodIndicator Light (Explosion-Proof Audible and Visual Alarm Light Optional)
Operating Temperature-40°C~70°C
Operating Humidity≤ 96% RH (No Condensation)
Pressure Range86kPa~106kPa
Installation MethodFixed Bracket Type, Pipe-Mounted Type, Wall-Mounted Type
Installation ThreadM20×1.5
Product Dimensions177mm×140mm×80mm
Explosion-Proof MarkEx db II C T6 Gb; Ex tb III C T80°C Db
IP RatingIP66
Executive StandardGB 15322.1-2019

Online

Phone

+86 137 5222 7265
+86 188 0644 0456

WeChat

Email

intl.trade@sdbenan.com

Top