GTYQ-SST626LED Point-type Combustible/Toxic Gas Detector

Detected Gases:Methane, Flammable Gases, Toxic Gases

Detection Principle:Catalytic Combustion, Infrared, Electrochemical,  Semiconductor

Display Type:None

Product Dimensions:116mm x 107mm x 108mm

Explosion-Proof Mark:Exdbib ll CT6Gb/ExtbIlCT80°CDb

Executive Standard:GB 15322.1-2019、GB12358-2024

GTYQ-SST626LED点型可燃/有毒气体探测器

Instruction Manual

Product Details
Specs & Params
Related Products

Product Description:

The GTYQ‑SST626LED gas detector continuously monitors methane, combustible gases and toxic gases within the lower explosive limit (LEL) range in industrial and commercial environments. It converts gas concentration and system information into digital signals and transmits them to the gas alarm controller for identification, display and processing.


Product Features

※ It adopts high-quality gas sensing elements with stable performance, high sensitivity, good anti-poisoning capability and strong anti-interference ability.

※ Two-wire non-polarity connection, no need to distinguish between positive and negative poles, simple and convenient installation with cost-effective wiring.

※It can be zero-calibrated and calibrated via the connected controller.

※ LED on-site status indication: green light for "Normal", yellow light for "Fault", and red light for "Alarm".


Application Scenarios:

Widely applied in large shopping malls, large restaurants, food processing factories, pharmaceutical factories, automobile manufacturing plants, small industrial and commercial users (small venues such as snack bars, hairdressing and beauty salons, hotels, public bathhouses and Internet cafes), farmers' markets and other industrial and commercial premises where gas leakage may occur.

Rated VoltageDC 36V
Detected GasesMethane, Flammable GasesToxic Gases
Detection PrincipleCatalytic Combustion, InfraredElectrochemical, Infrared, Semiconductor
Response TimeT90≤30sT90≤60s(for conventional gases)
Error±3%LEL±5%F.S(for conventional gases)
Communication MethodM-BUS Two-Bus
Display TypeNone
Power Consumption≤1W
Alarm MethodIndicator Light
Operating Temperature

Catalytic Combustion: -40°C~70°C; Electrochemical: -25°C~55°C;

Infrared: -40°C~70°C; Semiconductor: -40°C~70°C

Operating Humidity≤96%RH(No Condensation)
Pressure Range86kPa~106kPa
Installation MethodFixed Bracket Type, Pipe-Mounted Type, Wall-Mounted Type
Installation ThreadM20×1.5
Product Dimensions116mm×107mm×108mm
Explosion-Proof MarkExdbib ll CT6Gb/ExtbIlCT80°CDb
IP RatingIP66
Executive StandardGB 15322.1-2019GB 12358-2024