Operating Voltage: Main Power: AC220V±15%, 50Hz±1%; Backup Power: 12V DC, 3Ah
Power Consumption: ≤10W
Signal Input: M-BUS Two-wire Bus
Signal Transmission Distance: ≤800m
Installation Method: Wall-mounted
Operating Voltage: Main Power: AC220V±15%, 50Hz±1%; Backup Power: 12V DC, 3Ah
Power Consumption: ≤10W
Signal Input: M-BUS Two-wire Bus
Signal Transmission Distance: ≤800m
Installation Method: Wall-mounted
Product Description:
The SSK-ZL-YL32-E Pressure Controller is a practical and user-friendly device designed to monitor gas leaks and pipeline pressure. It forms a composite gas and pressure detection system with GTYQ-SST series detectors.
The SSK-ZL-YL32-E Pressure Controller is a non-explosion-proof product intended for installation in non-hazardous areas and adopts wall-mounted installation.
Product Features:
※ Equipped with a color LCD display and full Chinese menu operation.
※ Supports automatic fault detection with accurate indication of fault location and type.
※ Single-loop two-wire bus communication with non-polar signal design and automatic protection function, ensuring strong anti-interference performance, economical wiring and convenient installation.
※ Automatically identifies gas detectors and pressure detectors.
※ Built-in data storage module records alarm information and power on/off time data, with all stored data retained after power failure.
※ Features an RS485 bus communication interface for networking with the host computer control system to enable remote monitoring, significantly improving the timeliness and accuracy of monitoring.
※ Supports expandable 4G-CAT1 signal transmission for remote monitoring.
※ Built-in 2 groups of programmable relay contact signal outputs.
| Operating Voltage | Main Power: AC220V±15%, 50Hz±1%; Backup Power: 12V DC, 3Ah |
| Power Consumption | ≤10W |
| Signal Input | M-BUS Two-wire Bus |
| Connecting Cable | ≥RVVS 2*2.5mm2(Twisted Pair) |
| Signal Transmission Distance | ≤800m |
| Operating Temperature | -20℃~55℃ |
| Operating Humidity | ≤93%RH(Non-condensing) |
| Alarm Mode | Audible and Visual Alarm |
| Capacity | 32 Channels |
| IP Rating | IP30 |
| Communication Interface | RS485 Bus (Default Modbus/RTU Protocol Output) |
| Installation Method | Wall-mounted |
| Dimensions | 360mm × 280mm × 95mm |