Signal Input:4-20mA、M-BUS two-wire bus
Signal Output:Standard RS485 interface, default output with Modbus RTU protocol
Dimensions:620mm × 445mm × 130mm
Executive Standard:GB 16808-2008
Signal Input:4-20mA、M-BUS two-wire bus
Signal Output:Standard RS485 interface, default output with Modbus RTU protocol
Dimensions:620mm × 445mm × 130mm
Executive Standard:GB 16808-2008
Product Description:
SSK-ZL-F512-E Gas Alarm Controller is practical in function and easy to operate. It can form a gas alarm system with our company's 4-20mA gas detectors.
The SSK-ZL-F512-E controller is a non-explosion-proof product and shall be installed in non-explosion-proof areas by wall mounting.
Product Features:
※ Color LCD display with full Chinese menu operation.
※ 5-loop communication: loops 1–4 support 4–20 mA communication, loop 5 supports two-wire bus communication.
※ The 4–20 mA signal system features strong anti-interference capability; the two-wire bus adopts non-polarity design with automatic protection, enabling economical wiring and convenient installation.
※ Automatic fault detection, which can accurately indicate the fault location and type.
※ Automatically identifies detector types and alarm points, allowing monitoring of multiple detector types (%LEL/PPM/%VOL) on the same system without manual configuration.
※ Built-in large-capacity data storage, capable of recording 10,000 alarm records, 10,000 fault records and 1,000 operation records; data will not be lost after power failure.
※ RS485 bus communication interface (default Modbus RTU protocol), supporting networking with host computer control systems to realize remote monitoring, greatly improving the timeliness and accuracy of monitoring.
※ Built-in 3 groups of relay contact signal outputs.
| Operating Voltage | Main Power:AC220V±15%,50Hz±1% Backup Power: 12.8V 23Ah |
| Backup Power | Standard RS485 interface, default output with Modbus RTU protocol |
| Supported Detector Capacity | M-BUS detectors: ≤ 128 nodes (optional) 4-20mA detectors: ≤ 512 nodes (cabinet installation required for more than 48 nodes) |
| Power Consumption | ≤50W |
| Signal Input | 4-20mA, M-BUS two-wire bus |
| Signal Transmission Distance | ≤1000m(4-20mA branch RVS 3*1.5mm2 ,M-BUS branch RVS 2*2.5mm2) |
| Operating Temperature | 0℃~40℃ |
| Operating Humidity | ≤93%RH |
| Alarm Sound | 65dB ~ 115dB (at 1 meter directly in front) |
| Alarm Mode | Audible and visual alarm Audible alarm: two distinct sounds for fault alarm and concentration alarm respectively. Visual alarm: System status (alarm, fault) and power status (mains power fault, backup power fault, charging fault), etc., are indicated via LED indicators. |
| Weight | 13kg |
| Dimensions | 620mm×445mm×130mm (L×W×H) |